Emergency lighting testing: monthly and annual checks

The short answer

Emergency lighting needs a short functional test every month and a full rated-duration test once a year, usually three hours, with results recorded. BS EN 50172:2024 also calls for illuminance to be measured at five-year intervals.

The monthly test

A trained person briefly simulates a supply failure, usually with a test key switch, checks every emergency fitting and exit sign lights, then restores the supply and records the result. Many businesses do this in-house.

The annual test

Once a year the system runs on battery for its full rated duration. Every fitting must still be lit at the end. Because batteries need time to recharge afterwards, the test is best done at the end of the day.

Typical budgets for an annual test on a small system are £125–£400 per visit, excluding VAT.

Records

  • Keep a log book with dates, results and faults.
  • Record repairs and re-tests.
  • Keep design and installation certificates with the log.
  • Make records available for your fire risk assessment and any inspection.

Self-test and addressable systems

Self-test fittings run their own checks and show a status indicator, which reduces manual work, but someone still needs to check the indicators and keep records. Addressable systems report every fitting's status to a central panel, which suits larger sites.

Questions

What happens if a fitting fails the annual test?

It needs repair, usually a new battery or fitting, followed by a re-test. We give a fixed price for repairs at the time of the test.