Office lighting in Stonehouse
In short: glare-free LED lighting for desks, meeting rooms and receptions. For office lighting in Stonehouse we design to about 500 lux on desks, as BS EN 12464-1 suggests, and keep glare off screens by choosing the right optics rather than simply adding more light.

Local office lighting in Stonehouse
Reception areas in Stonehouse often need a warmer, layered look than the open-plan floor, with downlights or a feature pendant over the desk.
Offices in Stonehouse range from older suspended-ceiling floors with 600×600 fluorescent panels to newer exposed-soffit spaces where suspended linear LED looks and works better.
Our teams travel to Stonehouse from across Gloucestershire. Typical nearby jobs include Stroud, Dursley and Berkeley, so we can often combine survey visits.
Stonehouse at a glance
What's included
- LED panels, linear suspended fittings or downlights to suit your ceilings
- Emergency lighting checked and integrated with the new layout
- Out-of-hours installation so desks stay usable during the working day
- Layouts that hit around 500 lux on desks with low glare on screens
Guide prices in Stonehouse
Typical budgets for Stonehouse premises, supplied and installed, excluding VAT.
| Item | Guide budget (ex VAT) | Basis |
|---|---|---|
| LED panel (600×600) | £50 – £155 | per fitting, supplied and fitted |
| Presence (PIR) sensor | £40 – £80 | per sensor, installed |
| Daylight sensor | £60 – £120 | per sensor, installed |
| DALI dimming and control | £50 – £155 | per luminaire, on top of the fitting |
Example: 60 LED panels with presence sensing in a 600 m² open-plan office, about £3,650 – £10,400 excluding VAT. Fixed price after a free survey.
Rules that apply in Stonehouse
Approved Document L (2021 edition, with 2023 amendments) asks for new general lighting to average at least 95 luminaire lumens per circuit-watt, or to use the LENI method. The 2026 edition raises this to more than 105 for work under it from 24 March 2027.
In Great Britain, common T8 fluorescent tubes were caught by ecodesign rules from 1 September 2023 and the mercury exemptions for ordinary T5 and T8 lamps ended on 1 February 2024.
Privately rented commercial property in England generally needs an EPC of E or better, or a registered exemption, and lighting is one of the cheaper ways to improve a rating.
Stonehouse FAQs
Do you cover all of Stonehouse?
Yes. We work across Stonehouse and the GL10, GL5 and GL6 postcode districts, plus nearby places such as Stroud, Dursley and Berkeley.
Is the price fixed?
Yes. After the survey you get a fixed price for the scope agreed. If you add to the scope later, we price the extra before doing it.
How quickly can you survey in Stonehouse?
Most surveys in Stonehouse can be booked within a few working days. Tell us about any deadlines, such as a lease end or a fire risk assessment action, and we will try to fit around them.
Panels or linear pendants?
Recessed 600×600 panels suit suspended grid ceilings and are the simplest swap. Linear suspended fittings suit exposed soffits and can light both the desk and the ceiling, which makes a space feel brighter.
Office lighting near Stonehouse
- Office lighting in Stroud
- Office lighting in Dursley
- Office lighting in Berkeley
- Office lighting in Tetbury
- Office lighting in Gloucester
- Office lighting in Hucclecote