Warehouse lighting in Ely
LED high bays and aisle lighting for warehouses and distribution sites. For Ely sites with roof lights, daylight sensing can hold the high bays at a low level for much of a summer day.

Local warehouse lighting in Ely
Loading bays in Ely need good light at the dock edge and inside trailers. We often add dedicated dock lights alongside the high bay upgrade.
We plan lift access in Ely around your picking routes and loading times, so the warehouse keeps moving while the work is done.
For Ely premises we plan works around opening hours, deliveries and shared access, which matters on mixed-use estates and high streets.
Ely at a glance
What's included
- Lux checks after installation against the agreed design
- Presence sensing per aisle so empty aisles dim or switch off
- Lift and scaffold access planned around your operation
- Loading bay, dock leveller and yard lighting
Guide prices in Ely
Typical budgets for Ely premises, supplied and installed, excluding VAT.
| Item | Guide budget (ex VAT) | Basis |
|---|---|---|
| LED high bay | £145 – £390 | per fitting, supplied and fitted |
| LED batten (complete luminaire) | £80 – £195 | per fitting, supplied and fitted |
| Presence (PIR) sensor | £40 – £80 | per sensor, installed |
| Scissor or boom lift hire | £145 – £290 | per day |
Example: 60 LED high bays in a 3,000 m² warehouse, with 3 days of lift hire, about £9,150 – £24,150 excluding VAT. Fixed price after a free survey.
Rules that apply in Ely
The Welsh Approved Document L Volume 2 (2022) uses 95 luminaire lumens per circuit-watt for general lighting, with alternatives such as LENI. A new Welsh edition takes effect from 4 March 2027 with a higher figure of more than 105.
In Great Britain, common T8 fluorescent tubes were caught by ecodesign rules from 1 September 2023 and the mercury exemptions for ordinary T5 and T8 lamps ended on 1 February 2024.
Ely FAQs
Who does the work in Ely?
Work is carried out by vetted electricians working under S&K Property Investments and Improvement Ltd, which is responsible for the job and invoices you directly.
Which rules apply to lighting work in Ely?
Fire safety duties come from the Regulatory Reform (Fire Safety) Order 2005. For new lighting, the Welsh Approved Document L sets the energy efficiency requirements. We design and certify work to BS 7671 and, for emergency lighting, BS 5266-1.
Do you remove the old fittings in Ely?
Yes. Old fittings are removed, and fluorescent tubes are recycled as hazardous waste through an authorised route, with paperwork for your records.
What lux level does a warehouse need?
It depends on the task. BS EN 12464-1:2021 examples include 100 lux for stores and stockrooms, 150 lux at the floor of rack storage, 200 lux for open storage and loading, and 300 lux for packing and grouping.
Warehouse lighting near Ely
- Warehouse lighting in Cardiff
- Warehouse lighting in Rhiwbina
- Warehouse lighting in Pentyrch
- Warehouse lighting in Penarth
- Warehouse lighting in Pentwyn
- Warehouse lighting in Barry